Elbow/Jacket Sealing Kit, Rated 1-35kV



The Innovative Power Products EJSK kit is a heatshrinkable sealing kit used to seal premolded elbows and other devices to jacketed power cable. The kit seals the device to the cable’s jacket and mechanically reinforces the area. This added rigidity allows the operation of the elbows while reducing the amount of movement in the elbow/cable interface.

LVEC



Installation is fast and simple, no special skills required:

• Install the external grounding kit (if -G)
• Apply sealant strips
• Center jacketing tube; shrink in place
• Connect braid to device ground eyelet




The EJSK base kit includes everything necessary to seal jacketed power cables. Metallic tape, drain wire and UniShield® cables are all accommodated by the same kit.




  • To download a PDF copy of the data sheet Click here.

    For a complete PDF of the current IPP catalog Click Here. If you would like the catalog in a printed version, please go to the "Catalog Request" page via the link at the top of the page.

    EJSK Base Kit
    The EJSK base kit includes everything necessary to seal jacketed or unjacketed URD cables. Bare and jacketed concentric neutral cables are accommodated by the same kit.

    Each EJSK kit Contains:
    • Heatshrinkable jacketing tube
    • Sealant Strips
    • Parallel crimp connector
    • Installation Guide

    ESJK xG Kit
    The EJSK-xG kit includes everything necessary to seal jacketed power cables. Metallic
    tape, drain wire and UniShield® cables are all accommodated by the same kit.

    Each EJSK xG kit contains:
    • Heatshrinkable Jacketing Tube
    • Sealant Strip
    • Constant force spring (-G kits only)
    • Parallel crimp connectors
    • Solder-blocked tinned copper braid (-G kits only)
    • Copper grounding wire (-G kits only)
    • Installation Guide


ESJK & ESJK xG: Price List PL-730


Select the EJSK kit for the cable type, voltage class and conductor size of the cable. For metal tape, drain wire or UniShield® type cables, select the EJSK xG to have everything necessary to seal and reinforce the elbow-to-jacket interface.


Catalog # Sealing Sleeve Use Range
Conductor size (AWG/kcmil)
5kv 8kv 15kv 25kv 35kv
Metallic Tape/Wire Shielded Cables
EJSK-1G
0.75”-1.95” #2-500 #2-350 #2-250 #1-3/0  
EJSK-2G
0.95”-2.75” 600-1000 400-1000 300-1000 4/0-1000 1/0-1000
             
Jacketed URD Cables
EJSK-1
0.75”-1.95” #2-500 #2-350 #2-250 #1-3/0  
EJSK-2
0.95”-2.75” 600-1000 400-1000 300-1000 4/0-1000 1/0-1000
             

QUESTIONS OR QUOTES EMAIL US AT: sales@ippcorp.com or CALL TOLL FREE 1-800-544-4626