3/C, 35kV Medium Voltage Termination with Boot
Class 1 terminator for three-core 33-36kV extruded dielectric shielded power cable with up to 3 grounds


The Innovative Power Products MVT 43510 series Class I termination kits are heatshrinkable terminators for three-core armored or unarmored 35kV (33-36kV), extruded dielectric shielded medium voltage cables with or without ground wires. The MVT 43510E series terminations are for applications where the terminators are exposed to the elements such as precipitation or direct outdoor sunlight.

MVT 43510 series kits provide a lightweight compact alternative to other three-core termination methods. There are no compounds to mix and pour and no labor-intensive taping procedures. MVT 43510 series terminators provide a rugged, low cost and reliable cable termination.

  • MVT 43510 series kits are factory engineered to provide fast and easy installation with reliable performance.

    All MVT kits are designed to meet or exceed the requirements of IEEE-48 for Alternating Current Cable Terminations.

  • The MVT 43510 kits cover a wide range of conductor sizes and shapes. They accommodate out-of-round or off-tolerance cables, in both round and sector shaped conductors. The standard kits fit all types of three-core cable constructions with or without ground wires, including: metallic tape shield, drain wire shielded, lead covered and Unishield® power cables. MVT 43510 series kits can be used on armored cables when no separate armor terminator is used. The kits are based on the single-core MVT 3530 series kits with additional components to convert the three-core cable into three, individual single cores. The forty-eight inch (48”) tail length allows for easy training of the termination in switchgear, or at the riser in overhead transition applications. Three (3) kit sizes cover cable sizes from 1 AWG through 1500 kcmil.
MVES050
Electrical Specifications: 35kV Related Accessories
 
Test Requirement
Value MVT 43510
AC withstand, 1 minute (60 hz)
65 kV PASS
DC withstand, 15 minutes
105 kV PASS
Discharge Extinction Voltage (<3pC)
33.3 kV 33.3
Impulse withstand 1.2 x 50 μs (crest kV)
200 kV > 200kV
Wet withstand , 10 seconds
80 kV PASS
Dry withstand, 6 hours
75 kV PASS
Continuous current rating
= Cable = Cable
   
Bill of Materials: Std. Pkg: 1 kit = 1 each, 1-3/C cable end
 
Key
Item Description
Quantity Supplied
1
Field Control Material
3 strips In All Kits
2
Field Control Tubing
3 tubes In All Kits
3
Non-Tracking Tubing
3 tubes In All Kits
4
Sealant Strips
as required In All Kits
5
Core Jacketing Tubing
3 tubes In All Kits
6
Ground Jacketing Tubing
3 tubes In All Kits
7
Cable Breakout (3 leg)
1 each In All Kits
8
Cable Tie (U.V./Black)
1 each In All Kits
-
Installation Guide
1 each In All Kits
       
Options: Modification items for 1-3/C kit
     
Key
Item Description
Quantity Nomenclature
9
Non-Tracking Sheds
12 per kit E - Emod Kit**
10
Sealed Ground Kits
3 per kit G - Gmod Kit**
-
Cable Cleaning Kit (Not Shown)
1 per kit P - Pmod Kit**
-
Terminal Lugs
3 per kit Factory Quoted*



  • To download a PDF copy of the data sheet Click here.

    For a complete PDF of the current IPP catalog Click Here. If you would like the catalog in a printed version, please go to the "Catalog Request" page via the link at the top of the page.


The kits are packaged to provide one (1) three-core termination. Everything is included to terminate the three-core cable with or without ground wires less the terminal lugs and external grounding components. External grounding components can be included as a kit option. Connectors can be supplied in the kits; subject to factory quote. See section 5 for connector information.



  • MVT 43510: Price List PL-654

35kv Selection Guide
   
Conductor Range Catalog #

Insulation

Diameter

Jacket
Diameter Max.

1 - 3/0 AWG MVT 43511 1.00 - 1.25 1.75 - 3.75
4/0 - 750 kcmil MVT 43512 1.19 - 1.82 2.25 - 5.00
800 - 1500 kcmil MVT 43513 1.82 - 2.25 2.50 - 6.00
       

All dimensions in inches unless shown otherwise


Ordering Information

1. Select the kit catalog number by the cable size. The kit contains everything needed to terminate 3/C cable less the connectors for sheltered (indoor) use. Confirm the dimensions when at the extremes of the size range.
SPACE
2. Add the mod kit letter designation as needed to change the base kit:

E - sheds are required for exposed
(outdoor) environments. (Emod)
P - cable cleaning kit (Pmod)
G - sealed grounding kit (Gmod)
     
Examples
     
Example 1:
For 3/C, 2/0 AWG, 35kV cable without ground wires, in an exposed (outdoor) environment, with sealed grounding kits (Gmod) and cable cleaning kit:

MVT 43511 EGP - Product# Breakdown
435 -
400 series, 35kV termination kit
11 -
1-3/C term./box and kit size
E -
Exposed, Sheds included
G -
Sealed grounding kit
P -
Cleaning/prep kit

  Example 2:
For a 3/C armored, 250 kcmil, 35kV cable with 1, 2 or 3 grounds, installed in a sheltered (indoor) environment with sealed grounding kits and cleaning kit:

MVT 43512 GP - Product# Breakdown
435 -
400 series, 35kV termination kit
12 -
1-3/C term./box and kit size
G -
Sealed grounding kit
P -
Cleaning/prep kit



* CONNECTORS: To have connectors supplied in the kits, please refer to Section 5 in this catalog for connector selection information. The connectors must be ordered separately but can be packaged within the kits if detailed information is supplied.
** Supplied if specified.
*** WRAPAROUND SLEEVE with stainless steel channel– Contact IPP for more information.