3/C, 25kV Medium Voltage Termination without Boot
Class 1 terminator for 3/C armored 25-28kV extruded dielectric shielded cable using armor terminator


The Innovative Power Products MVTA 52510 series Class I termination kits are heatshrinkable terminators for three-core 25kV (22-28kV) armored extruded dielectric, shielded, high voltage power cables when an armor terminator is used to terminate and seal the cable’s armor and jacket. The MVTA 52510E series terminators are for applications where the terminators are exposed to the elements (outdoor).

MVTA 52510 series kits provide a lightweight, compact alternative to other three-core termination methods. The MVTA 52510 series kit makes installation of the armor terminator faster, easier and the system more reliable.

  • MVTA 52510 series kits are factory engineered to provide fast and easy installation with reliable performance.

    All MVT kits are designed to meet or exceed the requirements of IEEE-48 for Alternating Current Cable Terminations.

  • MVTA 52510 kits cover a wide range of conductor sizes and shapes. The standard kits fit all types of three-core armored cable constructions, including: metallic tape shield, drain wire shielded, lead covered and Unishield® cables. These kits are based on the single-core MVT 2530 series kits with core and ground wire tubings to jacket the exposed shields. The forty-eight inch (48”) tail length allows for easy training of the termination system in switchgear or at the riser in overhead applications. Three (3) kit sizes cover all cable sizes from 2 AWG through 1000 kcmil.

    If desired, a cable ‘through-passage’ fitting can be used to seal the cable jacket while allowing the jacketed cable to enter the enclosure. This fitting is less expensive than an armor terminator and much simpler to install. When a ‘through-passage’ device is used, the MVT 42510 termination should be used to protect and seal the system. This combination is generally less expensive than the use of armor terminators.

MVES050
Electrical Specifications: 25kV Related Accessories
 
Test Requirement
Value MVT 52510
AC withstand, 1 minute (60 hz)
65 kV PASS
DC withstand, 15 minutes
105 kV PASS
Discharge Extinction Voltage (<3pC)
21.5 kV 21.5
Impulse withstand 1.2 x 50 μs (crest kV)
150 kV > 150kV
Wet withstand , 10 seconds
60 kV PASS
Dry withstand, 6 hours
55 kV PASS
Continuous current rating
= Cable = Cable
   
Bill of Materials: (Std. Pkg (1 kit) terminates 1-3/C cable end
 
Key
Item Description
Quantity Supplied
1
Field Control Material
3 strips In All Kits
2
Field Control Tubing
3 tubes In All Kits
3
Non-Tracking Tubing
3 tubes In All Kits
4
Sealant Strips
as required In All Kits
5
Core Jacketing Tubing
3 tubes In All Kits
6
Ground Jacketing Tubing
3 tubes In All Kits
-
Installation Guide
1 each In All Kits
       
Options: Modification items for 1-3/C kit
     
Key
Item Description
Quantity Nomenclature
7
Non-Tracking Sheds
9 per kit E - Emod Kit**
8
Sealed Ground Kits
3 per kit G - Gmod Kit**
-
Cable Cleaning Kit (Not Shown)
1 per kit P - Pmod Kit**
-
Terminal Lugs
3 per kit Factory Quoted*



  • To download a PDF copy of the data sheet Click here.

    For a complete PDF of the current IPP catalog Click Here. If you would like the catalog in a printed version, please go to the "Catalog Request" page via the link at the top of the page.



The kits are packaged to provide one each (1) three-core termination. Everything is included to terminate the three-core armored cable less the terminal lugs, external grounding components and the armor terminator. External grounding components can be included as a kit option. Connectors can be supplied in the kits; subject to factory quote.



  • MVTA 52510: Price List PL-644

25kv Selection Guide
 
Conductor Range Catalog #

Insulation

Diameter

2 - 3/0 AWG MVT 52511 0.80 - 1.10
4/0 - 350 AWG MVT 52512 1.00 - 1.31
500 - 1000 kcmil MVT 52513 1.20 - 2.16
     

All dimensions in inches unless shown otherwise


Ordering Information

1. Select the kit catalog number by the
cable size. The kit contains everything
needed to terminate one 3/C armored
cable less the armor terminator and
connectors for sheltered (indoor) use. Confirm the dimensions when at the extremes of the size range.
SPACE
2. Add the mod kit letter designation as needed to change the base kit:

E - sheds are required for exposed
(outdoor) environments. (Emod)
P - cable cleaning kit (Pmod)
G - sealed grounding kit (Gmod)
     
Examples
     
Example 1:
For 3/C, armored 1 AWG, 25kV cable installed in an exposed (outdoor) environment, using a separately supplied armor terminator and adding sealed grounding kits (Gmod):

MVTA 52511 EG - Product# Breakdown
525 -
25kV Termination kit
11 -
1-3/C term./box and kit size
E -
Exposed, Sheds included
G -
Sealed grounding kit
 

  Example 2:
For a 3/C armored, 350 kcmil 25kV cable installed in a sheltered (indoor) environment using a separately supplied armor terminator and adding the grounding and cleaning kits:

MVTA 52513 GP - Product# Breakdown
525 -
25kV termination kit
13 -
1-3/C term./box and kit size
G -
Sealed grounding kit
P -
Cleaning/prep kit



* CONNECTORS: To have connectors supplied in the kits, please refer to Section 5 in this catalog for connector selection information. The connectors must be ordered separately but can be packaged within the kits if detailed information is supplied.
** Supplied if specified.
*** WRAPAROUND SLEEVE with stainless steel channel– Contact IPP for more information.